Section V Compatible Devices
V-4 P/N 446613 Issue I Rev. A
UL Compatible Four-Wire (Separately Powered) Smoke & Heat Detectors
Faraday
Detector
w/Base
Mfg. Detector
w/Base
Maximum
Standby
Current
Maximum
Alarm
Current
Notes
Air Products & Controls
9269 RW-DC-N 0.081mA 115mA Must use EOL Relay
9270 RW-DC-P 0.110mA 115mA Must use EOL Relay
Apollo Fire Detectors Limited
9259 w/9266 55000-150 w/45681-227 0.073mA 100mA Must use EOL Relay
9221 w/9266 55000-151 w/45681-227 0.073mA 100mA Must use EOL Relay
9274 w/9266 55000-152 w/45681-227 0.073mA 100mA Must use EOL Relay
9264 w/9266 55000-153 w/45681-227 0.073mA 100mA Must use EOL Relay
9261 w/9266 55000-250 w/45681-227 0.060mA 100mA Must use EOL Relay
9260 w/9266 55000-350 w/45681-227 0.125mA 100mA Must use EOL Relay
9222 w/9266 55000-380 w/45681-227 0.200mA 100mA Must use EOL Relay
System Sensor,
9377 1424 0.100mA 41mA Must use EOL Relay
9378 2424 0.120mA 41mA Must use EOL Relay
9379 2424TH 0.120mA 41mA Must use EOL Relay
9337 1112/24 0.050mA 25mA Must use EOL Relay
9338 2112/24 0.050mA 25mA Must use EOL Relay
9339 2112/24T 0.050mA 25mA Must use EOL Relay
9340 2112/24TSRB 15mA 45mA Must use EOL Relay
9358 w/9362 1451 w/B402B 0.120mA 41mA Must use EOL Relay
9359 w/9362 2451 w/B402B 0.120mA 41mA Must use EOL Relay
9360 w/9362 2451TH w/B402B 0.120mA 41mA Must use EOL Relay
9447 w/9362 5451 w/B402B 0.120mA 41mA Must use EOL Relay
9421 w/9362 4451HT w/B402B 0.120mA 41mA Must use EOL Relay
9164 DH400ACDCI 25mA 110mA Must use 6 wires
9165 DH400ACDCP 25mA 110mA Must use 6 wires
9175 6424 10mA 28.4mA Must use EOL Relay and 6
wires
Contact Type Heat Detectors
Faraday
Cat. No.
Mfg. Part
Number
Chemetron
9341 601
9342 602
9343 603
9344 604
9345 621
9346 622
9347 623
9348 624
9300-136 A-135
9300-190 A-200
9301-136 AT-135
9301-190 AT-200
PM2872-136 EPB501
PM2872-190 EPB502
PM2872-136F EPB503
PM2872-190F EPB504
Faraday
8858 8858
8859 8859
Notes:
1. Any U.L. Listed contact type heat detector with compatible contact
ratings is acceptable. The list to the left is provided for your
convenience.
2. For specific wiring and installation information, read the
instructions provided with each device.
Notes:
1. For specific wiring and installation information, read the
instructions provided with each device.
2. Each 9273 EOL Relay requires 15 mA standby current.