TECHNICAL DATA AND PERFORMANCES
Frame
1 2
Model
191 221 261 301 351 401
U.M.
Power supply
400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 V-ph-Hz
NOMINAL performances - Base setting up (VB) - Standard plants
Frame
1 2
Model
191 221 261 301 351 401
U.M.
Power supply
400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 V-ph-Hz
NOMINAL performances - Base setting up (VB) - Standard plants - EUROVENT certified data
Data declared according to EN 14511. The values are referred to units without options and accessories.
IR
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 19,9 22,1 25,8 30,8 35,6 40,2
kW
Power input 6,82 7,50 8,76 10,8 12,3 13,9
kW
EER 2,92 2,95 2,95 2,85 2,89 2,89
-
Water flow rate plant side 3432 3809 4444 5319 6143 6932
l/h
Pressure drops plant side 26 31 26 36 31 38
kPa
IP
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 19,5 21,7 25,3 30,2 34,9 39,4
kW
Power input 6,75 7,42 8,66 10,7 12,2 13,8
kW
EER 2,89 2,92 2,92 2,82 2,86 2,86
-
Water flow rate plant side 3363 3741 4358 5216 6023 6795
l/h
Pressure drops plant side 25 30 25 35 29 37
kPa
Heating A7W45 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 21,0 23,3 27,1 32,5 37,6 42,4
kW
Power input 6,49 7,14 8,33 10,3 11,7 13,4
kW
COP 3,24 3,26 3,25 3,16 3,21 3,16
-
Water flow rate plant side 3568 3961 4610 5515 6386 7188
l/h
Pressure drops plant side 27 33 27 38 33 41
kPa
Heating A2W45 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 17,4 19,3 22,5 26,8 31,0 35,0
kW
Power input 6,40 7,03 8,21 10,1 11,5 13,2
kW
COP 2,72 2,75 2,74 2,65 2,70 2,65
-
Water flow rate plant side 2954 3278 3825 4559 5276 5942
l/h
Pressure drops plant side 19 23 19 27 23 28
kPa
IR
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 20,0 22,2 25,9 31,0 35,8 40,4
kW
EER 2,97 3,00 2,99 2,92 2,96 2,95
-
Pressure drops plant side 26 31 25 36 30 38
kPa
ESEER 3,36 3,39 3,38 3,30 3,34 3,33
-
IP
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 19,6 21,8 25,4 30,4 35,1 39,6
kW
EER 2,94 2,98 2,97 2,90 2,93 2,91
-
Pressure drops plant side 25 30 25 34 29 37
kPa
ESEER 3,32 3,37 3,36 3,28 3,31 3,29
-
Heating A7W45 (air 7 °C bs - 6 °C bu / water 40 - 45 °C )
Heating capacity 20,9 23,2 27,0 32,3 37,4 42,1
kW
COP 3,27 3,30 3,29 3,20 3,25 3,21
-
Pressure drops plant side 28 34 27 39 33 41
kPa