TECHNICAL DATA AND PERFORMANCES
Frame
1 2
Model
191 221 261 301 351 401
U.M.
Power supply
400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 V-ph-Hz
NOMINAL performances - Low noise setting up (AS) - Standard plants
NOMINAL performances - Low noise setting up (AS) - Standard plants - EUROVENT certified data
IR
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 19,1 21,2 24,8 29,6 34,2 38,6
kW
Power input 7,34 8,09 9,42 11,6 13,3 15,0
kW
EER 2,60 2,62 2,63 2,55 2,57 2,57
-
Water flow rate plant side 3295 3655 4273 5113 5903 6658
l/h
Pressure drops plant side 24 29 24 33 28 36
kPa
IP
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 18,7 20,8 24,3 29,1 33,6 37,8
kW
Power input 7,27 8,00 9,33 11,4 13,1 14,9
kW
EER 2,57 2,60 2,60 2,55 2,56 2,54
-
Water flow rate plant side 3226 3586 4187 5010 5783 6520
l/h
Pressure drops plant side 23 28 23 32 27 34
kPa
Heating A7W45 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 19,9 22,2 25,8 31,0 35,8 40,3
kW
Power input 6,22 6,85 7,98 9,88 11,3 12,8
kW
COP 3,20 3,24 3,23 3,14 3,17 3,15
-
Water flow rate plant side 3381 3773 4388 5259 6078 6847
l/h
Pressure drops plant side 25 30 25 35 30 37
kPa
Heating A2W45 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity 16,4 18,3 21,3 25,5 29,5 33,2
kW
Power input 6,13 6,74 7,87 9,73 11,1 12,6
kW
COP 2,68 2,72 2,71 2,62 2,66 2,63
-
Water flow rate plant side 2800 3107 3620 4337 5020 5651
l/h
Pressure drops plant side 17 21 17 24 21 26
kPa
Frame
1 2
Model
191 221 261 301 351 401
U.M.
Power supply
400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 V-ph-Hz
IR
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 19,2 21,3 24,9 29,8 34,4 38,8
kW
EER 2,64 2,67 2,67 2,61 2,63 2,62
-
Pressure drops plant side 24 29 24 33 28 35
kPa
ESEER 2,98 3,02 3,02 2,95 2,97 2,96
-
IP
Cooling A35W7 ( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity 18,8 20,9 24,4 29,2 33,7 38,0
kW
EER 2,61 2,64 2,64 2,58 2,59 2,59
-
Pressure drops plant side 23 28 23 32 27 34
kPa
ESEER 2,95 2,98 2,98 2,92 2,93 2,93
-
Heating A7W45 (air 7 °C bs - 6 °C bu / water 40 - 45 °C )
Heating capacity 19,8 22,1 25,7 30,8 35,6 40,1
kW
COP 3,22 3,28 3,26 3,17 3,21 3,18
-
Pressure drops plant side 25 31 25 35 30 38
kPa
Data declared according to EN 14511. The values are referred to units without options and accessories.