14
TECHNICAL DATA AND PERFORMANCES
Frame
1 2
Model
191 221 261 301 351 401
U.M.
Power supply
400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 400 - 3N - 50 V-ph-Hz
NOMINAL performances - Low noise setting up (AS) - Radiant plants
IR
Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 23,7 26,2 30,7 36,7 42,4 47,7
kW
Power input 7,62 8,41 9,79 12,0 13,8 15,6
kW
EER 3,11 3,12 3,14 3,06 3,07 3,06
-
Water flow rate plant side 4087 4534 5307 6354 7333 8261
l/h
Pressure drops plant side 36 43 36 50 43 54
kPa
IP
Cooling A35W18 ( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity 23,2 25,7 30,1 35,9 41,5 46,7
kW
Power input 7,55 8,32 9,69 11,9 13,7 15,5
kW
EER 3,07 3,09 3,11 3,02 3,03 3,01
-
Water flow rate plant side 4002 4448 5204 6217 7179 8089
l/h
Pressure drops plant side 34 42 34 48 41 51
kPa
Heating A7W35 ( source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 20,3 22,6 26,3 31,6 36,5 41,2
kW
Power input 5,24 5,77 6,73 8,34 9,49 10,9
kW
COP 3,87 3,92 3,91 3,79 3,85 3,78
-
Water flow rate plant side 3463 3857 4491 5383 6223 7011
l/h
Pressure drops plant side 26 32 26 37 31 39
kPa
Heating A2W35 ( source : air in 2°C d.b. 1°C w.b. / plant : water in 30°C out 35°C )
Heating capacity 16,8 18,8 21,8 26,2 30,2 34,0
kW
Power input 5,16 5,67 6,61 8,19 9,32 10,6
kW
COP 3,26 3,32 3,30 3,20 3,24 3,21
-
Water flow rate plant side 2880 3206 3720 4474 5160 5811
l/h
Pressure drops plant side 18 22 18 26 22 27
kPa
Data declared according to EN 14511. The values are referred to units without options and accessories.