EasyManua.ls Logo

Festo CPX-FB43 - Technical data; General

Festo CPX-FB43
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Festo — CPX(-M)-FB33/34/35/43/44/45 — 2022-05f
Technical data
35
10 Technical data
10.1 General
Characteristics Bus node
General technical data è CPX system description CPX-SYS-…
Degree of protection by
housing,
in accordance with IEC 60529,
completely mounted, plug
inserted or cover cap installed.
IP65/IP67
Protection against electric
shock
By PELV circuits.
PELV = Protected Extra-Low Voltage
Tab. 26: General characteristics
Characteristics CPX-FB33 CPX-M-FB34 CPX-M-FB35
Module code in the CPX Ter-
minal
Remote I/O
Remote Controller
215
164
216
165
217
166
Module identification
Remote I/O FB33-RIO PROFINET
remote I/O
FB34-RIO PROFINET
RJ45 remote I/O
FB35-RIO PROFINET
LWL remote I/O
Remote Controller FB33-RC PROFINET
I/O bus node
FB34-RC PROFINET
RJ45 bus node
FB35-RC PROFINET
LWL bus node
Power supply
Operating voltage/load voltage è CPX system description (CPX-SYS-…)
Internal current consumption of
the internal electronics at a
nominal operating voltage of 24
V DC,
from operating voltage supply
for electronics/sensors, U
EL/SEN
Typ. 85 mA Typ. 85 mA Typ. 155 mA
Separation of the PROFINET
interfaces to U
EL/SEN
Electrically isolated
by transformer up to
1500 V
Electrically isolated
by transformer up to
1500 V
Electrically isolated
by fibre-optic cable
Mains buffering time 10 ms 10 ms 10 ms
Tab. 27: Special characteristics of CPX-(M)-FB33/34/35