Doc. P/N 8.8517.00.6
Rev. December, 2019
Connection of 4…20 mA line
incorrect
No supply voltage over
4…20 mA line
Supply voltage too low
(min. 8 V DC)
Error current
<3.6 mA or >21 mA
Connection of 4…20 mA line
incorrect
No supply voltage over
4…20 mA line
Measuring value inaccurate/
incorrect
Offset drift, electronic defect
Return to Fike for recalibration and
response test
Product build-up on the
detector membrane
clean (refer to routine inspection section)
6. DE-COMMISSIONING PROCEDURE / CHECK-LIST
De-commissioning should only be performed by a Fike qualified Service Engineer, who has been assigned to prepare
and complete the de-commissioning of the Explosion Protection System.
Each step in a listed procedure must be adhered to and completion/acceptance of a listed form is mandatory. In the
case of non-compliance, the observed discrepancy must be corrected before completion of the system de-
commissioning.