51
Battery Calculations
Appendix A
Battery Calculations
Use the Total Standby and Alarm Load Currents calculated in Table A-2 and Table A-3 for the following battery
calculation.
Note:
1. 7 Ampere Hour battery can be located in the backbox.
2. Batteries larger than 7 Ampere Hour, up to 18 Ampere Hour, require the BB-17F battery box.
TABLE A-1: Battery Calculation
Standby Load
Current (amps)
[ ]
X
Required Standby Time in Hours
(24 or 60 Hours)
[ ]
= _______________
Alarm Load
Current (amps)
[ ]
X
Required Alarm Time in Hours
(i.e. 5 min. = 0.084 hours)
[ ]
= _______________
Add Standby and Alarm Load for Required Ampere Hour Battery = _______________
Multiply by derating factor of 1.2 X 1.2 _______________