17
Linked delay: See the same option in the section
Outputs programming.
For the following types of devices, FC410LPAV (all
versions), FC430LPASB, FC430SAB (with FC430SB), in
addition those devices certified to EN54-23, FC410LPS-
R/W, FC410LPBS, FC430LPBSB, you can separate the
sounder and beacon programming into two different
programming tabs. These programming tabs have the
same programming options, except for Set as SC1 that will
only be present for the sounder output.
Note: It is not possible to separately enable or disable the
two output channels.
Note: The separate sounder and beacon programming of
the devices above is also possible using the Control panel
user interface in the Devices programming pages.
Pulse on
If the Pulse on option is disabled, the sounder rings
steadily. If not, the sounds rings 2 seconds on, 2 seconds
off, as indicated by the options below. In all cases, the
sounder tone is based on the selection in the Options
page.
Note: The sounder rings continuously for the Fault, Double
Knock and Test events.
Note: Disable As general options to make the Pulse on
options of the selected sounder different to the settings in
the General outputs settings screen.
Detector alarm
If enabled, the sounder will ring when the programmed
Alarm event is triggered by a detector. The default status
is disabled.
Note: The sounder will ring continuously when the
programmed Alarm event is triggered by a callpoint or
Evac button, independently by the Detector alarm option
set.
Delay to alarm
If enabled, the sounder rings when the programmed Delay
to alarm event occurs. The default status is disabled.
Warning
If enabled, the sounder rings when the programmed
Warning event occurs. The default status is enabled.
Sounder options
In the loop sounders programming page, there are three
controls to set the Tone, Volume and the Beacon
frequency for Alarm, Delay to alarm and Warning event
types so that each event type causes a different sound or
LED blinking. If different types of trigger events are active
at the same time for a sounder, this rings with the highest
priority tone.
Note: Disable As general options to make the Sounder
options of the selected sounder different to the settings in
the General outputs settings screen.
Default volumes
Maximum for Alarm and Delay to alarm, minimum for
Warning.
Default beacon frequencies
0.5Hz.
Multiple input-output module-parameters programming
(FC410MIO/FC410QIO)
Click on the Multiple input/output module entered,
FC410MIO, three inputs and four outputs module, or
FC41OQIO, four inputs and four outputs module, see the
customised manuals, and the relevant programming
window will appear.
The options descriptions are the same as the Input and
Output modules paragraphs. In the field Label, a
description of Input/Output module will be inserted. For
trigger points, see the same section in Output module
parameters programming.
Options section
Opps interface: ActUnit/KeySafe allows you to
manage the procedure for the automatic opening
of the factory, office, shop, warehouse doors in
case of fire. This avoids the breakage of these
structures. The module outputs can control these
actions.
LED blinking: Click on this to enable or disable
signalling LED. The FC410TSM door control
module, one input or one output, closes a fire door
in the case of an alarm or a fault. The FC410TSM
monitors the external power supply and loop
voltage test, if the relevant option is enabled.
Note: In an eventual connection on the right side, a two
wires connection, the module enables the yellow isolator
LED blinking. This signals an incorrect installation.
Manual callpoint parameters programming
Click on the Manual callpoint, FC420CP and FC421CP,
the relevant programming will appear as per the following
description. The General section is the same as the
Detectors section.