23
Network
Figure 14: Network tab
In the Network section, a tick means you can perform the
following actions:
Enable network
Allow buzzer silence silences a device that is
activated in every part of the network.
Allow Network Commands enables the Control
panels to do the commands (Reset, Silence,
Investigate) programmed in other network control
panels.
Enable repeaters and FC500 MFI modules in the
Network repeaters section and Network MFI
section.
One click only means the repeater, FC500MFI
and Client panels are present, but not enabled.
A double click means the repeater, FC500MFI
and Client panels are enabled.
For the FC500MFI module, see the chapter Programming
from the panel section in the Installation manual.
Note: You can insert the repeater address from the panel.
See the chapter Programming from the panel in the
Installation manual.
Delays and Thresholds
In this section, you can program:
The Alarm Delays; you can select five timers.
When selecting the output in the Panel outputs
screen, the timer is set in the Linked delay option.
The Panel Delays.
Investigation Time; When you press the
Investigate Key, a Delay is added automatically to
the Delay to alarm remaining delay.
Note: The sum of Investigation time and Delay to alarm
time must not exceed 10 minutes.
Fault delay
This field controls how long it takes the panel to signal a
Mains failure. The amber signalling LED (or power supply
fault) and the relevant event will appear on the display. For
the Delay to alarm duration, an input device programmed
with Delay to alarm time generates and Alarm status when
the Delay to alarm time elapses.
Delay to alarm signals include:
An audible signal emitted by the control panel.
Blinking on the Delay to alarm LED; this LED is on
the repeater FC500 only.
The display message.
The activation of outputs with programmed delay
to alarms.
Silence duration
When the control panel is in Night mode, the Silence delay
is the maximum silence time of the outputs. To disable the
Silence duration time, click the checkbox Disabled located
to the right of Time value entry.