24
Reset
Program the Reset time; the minimum time is 2 seconds
and the maximum time is 15 seconds.
Monostable outputs time
When the monostable option is set for the outputs, the
Monostable outputs time defines, for the entire system, the
period of time for which the outputs remain active once
triggered. Values range from 1 to 30 minutes; the default
value is three minutes.
Warning sound duration
This is the numeric value defining the activation time of
outputs that have the Timed warning option set. The value
is valid for the entire system; every new trigger event of
the programmed outputs restarts it.
Range: From 3 to 60 seconds
Default value: 5 seconds
Resolution: 1 second
Thresholds
The Thresholds section is reserved for the DDM gas
detector.
Set: This function allows you to choose between
four levels of threshold.
General outputs settings
In this section, the behaviour of the Sounder circuit 2
(SC2) and the loop sounders can be configured at a
system level. These configurations apply to the SC2 loop
sounder when As general options is enabled.
Pulse on
If the Pulse on option is disabled, the sounder rings
steadily. If not, the sounder pulses (2 seconds on, 2
seconds off) as indicated by the following options. In all
cases, the sounder tone is based on the selection in the
Panel settings for symphony sounders and Panel settings
for AV base sounders sections.
Note: The sounds always rings continuously for the Fault,
Double knock and Test events.
Detector alarm
If enabled, the sounder pulses when the programmed
Alarm event is triggered by a detector. The default status
is disabled.
Note: The sounder rings continuously when the Alarm
event is triggered by a call point or the EVAC button,
independent of the Detector alarm option set.
Delay to alarm
If enabled, the sounder pulses when the programmed
Delay to alarm event occurs. The default status is
disabled.
Warning
If enabled, the sounder pulses when the programmed
Warning event occurs. The default status is enabled.
Panel setting for symphony sounders and panel setting
for AV base sounder
For each of the trigger events, Alarm, Delay to alarm and
Warning, you can select the Sounder tone, volume, the
beacon flash rate default tones; these default zones
include 7Hz Fast sweep (Dutch slow whoop if you select
Dutch language) for Alarm and Delay to alarm, 2 tone for
Warning. Default volumes include maximum for Alarm and
Delay to alarm, minimum for Warning. Default beacon
frequencies is 0.5Hz.
Communicators programming
The Communicators screen is for programming the
parameters of the PSTN interface, of the FC500IP module
and of Panel events, as described below.
PSTN interface
The PSTN interface section activates, after the PSTN
telecom interface is enabled on the General options
screen; see Figure 13.
Options
In the Options section:
Call attempts: Set the maximum number of
attempts that the PSTN interface makes for each
telephone number. Set from one to nine, three is
the default number of attempts you can make.
Iterations: Set the number of times the PSTN
interface repeats the voice message; set from one
to nine, the default setting is three.
Tone check: If enabled, the PSTN interface
controls whether it obtains a Dialling tone and if it
can obtain the tone to move to the next step. If
not, it considers the phone call failed; hang up and
try again.
Call all telemonitoring: If the Call all
telemonitoring numbers option is enabled, the
PSTN interface calls all numbers programmed for