19
Communicators programming
The Communicators screen is for programming the
parameters of the PSTN interface, of the FC500IP module
and of Panel events, as described below.
PSTN interface
The PSTN interface section activates, after the PSTN
telecom interface is enabled on the General options
screen; see Figure 12.
Options
In the Options section:
Call attempts: Set the maximum number of
attempts that the PSTN interface makes for each
telephone number. Set from one to nine, three is
the default number of attempts you can make.
Iterations: Set the number of times the PSTN
interface repeats the voice message; set from one
to nine, the default setting is three.
Tone check: If enabled, the PSTN interface
controls whether it obtains a Dialling tone and if it
can obtain the tone to move to the next step. If
not, it considers the phone call failed; hang up and
try again.
Call all telemonitoring: If the Call all
telemonitoring numbers option is enabled, the
PSTN interface calls all numbers programmed for
the previous event, up to the time all telephone
calls succeed, or at most, for the numbers of call
attempts programmed. If the Call all telemonitoring
numbers options is disabled, the PSTN interface
will interrupt the call as soon as it succeeds.
Call all voice messages: If the Call all voice
messages numbers option is enabled (default
setting), the PSTN interface calls all programmed
numbers for the previous event, until all phone
calls succeed according to the numbers of call
attempts programmed. If the Call all voice
messages is disabled, the PSTN interface will
interrupt the calls as soon as one is successful.
Play message after
The section Play message after sets the condition for the
voice message playback.
Dialling: Message playback occurs as soon as
the telephone number is dialled.
Voice: Message playback occurs when the PSTN
interface detects a voice answer.
Delay: Message playback occurs when the
programmed delay elapses after the telephone
number is dialled. You can set the delay from 0 to
99 seconds, with 1 second steps. The default
setting is 0 seconds.
Periodic report
The section Periodic report sets the parameters
corresponding to the Period test as described below.
Date and time first test: Set the date and time for
the first Periodic test.
Period: Set the interval between two periodic
tests. You can set the interval from 1 up to 25
hours, in steps of 1 hour. The default setting is 24
hours.
Note: The Periodic test event is not recorded in the Events
log.
Address book
The section Address book programs the telephone
numbers that you can use to send:
Voice messages: Dialler function and
telemonitoring data occur when the events are
recognised by the panel.
In the case of Telemonitoring, select:
The type of protocol (SIA, ADEMCO Contact ID)
and customer code.
Phone numbers are only for alarms, faults and numbers of
general use.
Voice messages
In the section Voice messages, parameters relating to
voice messages are programmed, as described below.
(1-7) Messages: You cannot edit messages 1 to 7.
(8-32) Messages: You can assign a maximum 20
characters description to messages 8-32.
Table 9: Icons in the Voice messages section
Icon
Note: A USB memory stick is the only way to download
audio files from the panel.