14. Manual Fire and Fault Tests
After installation or cleaning, it is recommended that a manual Fire and Fault test is
performed:
Fire Test: Cover the Reflector slowly so that it takes longer than 5 seconds to cover. The
System Controller will signal Fire to the Fire Control Panel after the delay to fire has expired
(10s default)
Fault Test: Cover the Reflector completely within 2 seconds. The System Controller will signal
Fault back to the Fire Control Panel after the delay to fault has expired (10s default)
Detector Fire LED Test
Detector will signal Fire,
System Controller will stay
Normal.
Press to exit
without performing the test
Relay/Controller Wiring Test
System Controller signals
‘Fire’ to Fire Control Panel
Press or to
exit
It is possible to perform a Fire Test from the System Controller, to test the wiring to the Fire
Control Panel
NOTE: The Remote Fire Test is acceptable for Fire Authority Acceptance and Routine
Maintenance per UL268-5
15. Remote Fire Test
11

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fireray 5000 and is the answer not in the manual?

Fireray 5000 Specifications

General IconGeneral
Operating Temperature-10°C to +55°C
IP RatingIP65
Detection PrincipleInfrared beam
Alarm OutputFire and Fault relays
CertificationEN54-12
WavelengthInfrared