All installations should comply with local regulations
For detectors approved to UL268 refer to NFPA72 for installation guidance. In such
installations, it is advised that the maximum distance of Detector and Reflector from the
ceiling must be 10% of the distance between floor and ceiling
For installations covering less than 18m, the Short Range Mask must be used
Position beam as high as possible, but with a minimum distance of 0.5m from Detector and
Reflector to ceiling.
Mount Detector and Reflector directly opposite each other
Do NOT position Detector where personnel or objects can enter the beam path
Do NOT position 2 Detectors facing each other
Detector LED indicator must face downward
Do NOT install the Detector or Reflector in environments where condensation or icing are
likely to occur
1850m = 1
50100m = 4
818m = 1
Use Short Range
Mask
50cm
8-100m
50cm
Ensure clear line of
sight from Detector
to Reflector
Mount on solid surfaces (structural wall or girder)
50cm
50cm
8-100m
2
1. General Information

Related product manuals