MarkIII: Manual Rebooting Method
If required, here is the procedure to manually reboot the MarkIII:
1- Turn OFF all disconnecting means to de-energize the MarkIII. The MarkIII's screen should turn black.
2- Press the stop button or wait until the MarkIII's LED extinguishes.
3- Wait 10 seconds.
4- Turn ON all disconnecting means.
Pressure Transducer Test
The controller will test the pressure transducer at least once a week if no manual run test or no weekly test has been
conducted. During the test, the pressure reading will drop to zero but the controller will not see it as a starting request.
This pressure drop will be recorded in the “Pump Curve” page and in the logs with the message.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Firetrol FTA1100 Series and is the answer not in the manual?

Firetrol FTA1100 Series Specifications

General IconGeneral
TypeFire Pump Controller
Phase3-Phase
Frequency50/60 Hz
Humidity Range0-95% non-condensing
EnclosureNEMA 4, NEMA 4X
Pump TypeElectric Fire Pump
Output CurrentVaries by HP rating
DimensionsVaries by model and enclosure type