Fisher & Paykel 635 Active Smart - Compressor will Not Run and Is Hot to Touch; Compressor Electrical Tests

Fisher & Paykel 635 Active Smart
145 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
321144
141
Refer to Section 4.18
When defrost sensor
reaches +8 degrees C (46
degrees F) the compressor
will start
Has the
system gone
into defrost
mode?
Is current
being drawn
by defrost
element?
Yes
Check compressor
and system for
leaks/blockages and
repair as required
Yes
No
Remove FC cover.
Is there a full frost
pattern on the
evaporator?
Yes
No
16.12 Compressor Will Not Run And Is Hot To Touch
16.13 Compressor Electrical Tests
Are
compressor
winding
resistances
OK?
Yes
No
Replace
compressor
Are electrical
connections
to
compressor
OK?
Substitute
power/control
module
Repair connections
No
Yes