EasyManuals Logo

Fisher FIELDVUE DVC6200 Quick Start Guide

Fisher FIELDVUE DVC6200
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #32 background imageLoading...
Page #32 background image
Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
January 2017
32
Smart Wireless THUM Adapter
Refer to the Smart Wireless THUM Adapter quick installation guide (0082501004075) for additional information.
Note
The recommended mounting orientation for the THUM Adapter is vertically up, as shown in figure 26, for optimal wireless
communication range.
Figure 26. THUM Adapter Installed On DVC6200 Digital Valve Controller
TOP CONDUIT
ENTRANCE
X0433
1. Remove the DVC6200 terminal box plug from the top conduit entrance.
2. Thread the THUM Adapter into the top conduit entrance.
3. Using the wire splice included with the THUM Adapter (or other suitable wire splice), connect the wires as shown in
figure 27 below.
Figure 27. Wiring the THUM Adapter
GG18677
THUM ADAPTER
GREEN
RED
BLACK
WHITE
YELLOW
WIRED DEVICE
LOOP -
LOOP +
SPLICE
CONNECTOR
GROUND
4-20 mA
4-20 mA
LOOP -
LOOP +
4. Carefully coil the wires inside the terminal box.
5. Replace and hand tighten the cover on the terminal box.
6. Proceed to Step 4—Configure the Digital Valve Controller on page 33.

Other manuals for Fisher FIELDVUE DVC6200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fisher FIELDVUE DVC6200 and is the answer not in the manual?

Fisher FIELDVUE DVC6200 Specifications

General IconGeneral
TypeDigital Valve Controller
Operating Temperature Range-40 to 85 °C (-40 to 185 °F)
Enclosure RatingNEMA 4X, IP66
Input Signal4-20 mA, HART
Communication ProtocolHART
Supply Pressure1.4 to 7 bar (20 to 100 psi)
DiagnosticsValve signature
ApprovalsATEX, IECEx, FM, CSA
Power SupplyLoop powered

Related product manuals