Limitorque MX Electronic Actuator FCD LMENIM2350-02 A4 – 05/16
32
FLOWSERVE PROPRIETARY INFORMATION
Use or disclosure of this information is subject to the restrictions on the title page of this document
11.1.2 Local Command Override
Default = LOCAL>ESD
Select “NO” to choose:
“ESD>LOCAL” – ESD overrides local command to operate actuator
“LOCAL>ESD” – Local command to operate actuator overrides ESD
11.1.3 Stop Override
Default = STOP>ESD
Select “NO” to choose:
“ESD>STOP” – ESD overrides stop command
“STOP>ESD” – Stop command overrides ESD
11.1.4 Jammed Valve Override
Default = JAMMED VALVE>ESD
Select “NO” to choose:
“ESD>JAMMED VALVE” – ESD overrides jammed valve indication
“JAMMED VALVE>ESD” – Jammed valve indication overrides ESD (default)
11.1.5 Lost Phase Override
Default = LOST PHASE>ESD
Select “NO” to choose:
“ESD>LOST PHASE” – ESD overrides lost phase indication
“LOST PHASE>ESD” – Lost phase indication overrides ESD
11.1.6 Over-Torque Override
Default = OVERTORQUE>ESD
Select “NO” to choose:
“ESD>OVERTORQUE” – ESD overrides over-torque situation
“OVERTORQUE>ESD” – Over-torque situation overrides ESD
11.1.7 Motor Thermostat Override
Default = ENABLED
Select “NO” to choose:
“ESD>THERMOSTAT” – ESD overrides Motor Thermostat tripped
“THERMOSTAT>ESD” – Motor Thermostat tripped overrides ESD
NOTE: Disabling the motor thermostat voids all third-party certifications including Factory Mutual, CSA, IECex
and ATEX. Disabling the motor thermostat removes protection from overheating the motor and may cause unsafe
conditions.