5.6 Remote Mount
The Logix 3800zb can be remote mounted away from the
actuator using the Flowserve Zero Bleed Automation Package
and the Flowserve Logix Remote mount P/N LGENIM0001-
01. See Figures 12 and 13.
The Logix 3800zb positioner can also be separately mounted
in a customer specific remote mount application. The end user
would supply their own 4-Way solenoid-controlled valve and
remote mount feedback. See section 16 for valve and
feedback unit requirements.
Figure 12: Logix 3800zb Automation Package
Figure 13: Logix Remote Mount Valtek Linear
mounting example
The tubing requirements are the same for the remount mount
options as defined in sections 5.1 through 5.5.
NOTE: The tubing run for remote applications is restricted
to a maximum length of 100ft.