Insulation Tester
General Specifications
5
General Specifications
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73.5 mm x 104 mm
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 x AA alkaline IEC LR6
Dimensions (H x W x L) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184 mm x 211 mm x 93 mm
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.3 kg
Temperature
Operating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .-10 °C to +50 °C
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -20 °C to +60 °C
Operating Humidity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Non condensing (<10 °C)
80 % RH (at 10 °C to 30 °C)
50 % RH (at 30 °C to 50 °C)
Altitude
Operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2000 m
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 000 m
Overvoltage Category. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CAT IV 600 V
Safety
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 61010-1: Pollution Degree 2
IEC 61010-2-033: CAT IV 600 V
IEC 61557-1
Insulation Resistance Measurement. . . . . . . . . . . . . . . . . IEC 61557-2
Effectiveness of the Protective Measures. . . . . . . . . . . . . IEC 61557-16
Intrusion Protection (IP) Rating . . . . . . . . . . . . . . . . . . . . . IEC 60529: IP40
Electromagnetic Compatibility (EMC)
International . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 61326-1: Portable Electromagnetic Environment
IEC 61326-2-2 CISPR 11: Group 1, Class A
Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the
internal function of the equipment itself.
Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power
supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic
compatibility in other environments due to conducted and radiated disturbances.
Caution: This equipment is not intended for use in residential environments and may not provide adequate protection to radio
reception in such environments.
Number of Insulation Resistance Measurements
Un (V) R
load
(Ω) Number of Measurements
250 V 250 kΩ 6500
500 V 500 kΩ 3800
1000 V 1 MΩ 2200
2500 V 2.5 MΩ 1300