EasyManua.ls Logo

Fluke 1625 - Earthing Resistance Measuring Method

Fluke 1625
90 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1625
Users Manual
78
Measuring Method
The current voltage measuring method is based on the block diagram circuit
shown in the figure below.
U meas.
V
G
I
E
ES
S
E
S
R
S
R
E
U
E
I
H
H
R
H
edw057.eps
An AC generator G feeds current I via earth electrode E (earth electrode resis-
tance R
E
) and auxiliary earth electrode H (auxiliary earth electrode resistance
R
H
).
Voltage U
E
drops on earthing resistance R
E
(U
E
proportional to R
E
.) This volt-
age is picked up and measured by probe S. With the so called three wire cir-
cuit, the instrument sockets E and ES are connected to each other. In a four
wire circuit an separate cable is used to connect socket ES with the earth elec-
trode.
With that, the voltage drop of the cable between socket E and earth electrode is
not measured. As the voltage measuring circuit has such a high impedance, the
influence by the probe resistance R
S
is neglectable within certain limits.
Thus the earthing resistance evolves
1
Meas
E
U
R =
and is independent from the resistance of the auxiliary earth electrode R
H
. The
generator runs at a frequency between 70 and 140 Hz.
It has to hold a minimum distance of 5 Hz to one of the nominal frequencies
between 16 2/3, 50 or 60 Hz and their harmonic waves. A frequency selective
filter adjusted to the generator frequency is inserted.

Table of Contents

Related product manuals