Foster FD2-10 - FD2-10 Controller Parameter Details; Parameter Values for Foster FD2-10 Controller

Foster FD2-10
23 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
FOSTER FD2-10
FPS2HR
FPS3HR
FPS4HR
FPS5HR
Reg
Par
Min
Mid
Max
Description
C
C
C
C
253
SCL
1
o
C
o
F
2
o
C
Readout scale.
C
C
C
C
200
SPL
-50
o
…..
SPH
Minimum limit for SP setting.
1
1
1
1
202
SPH
SPL
…..
120
o
Maximum limit for SP setting.
3
3
3
3
204
SP
SPL
…..
SPH
Temperature setpoint to be achieved.
1
1
1
1
268.1
C-H
REF
…..
HEA
Temperature control mode.
REF
REF
REF
REF
214
HYS
1
o
…..
10
o
Off / On thermostat differential.
4
4
4
4
216
CRT
0 min
…..
30 min
Compressor rest time.
2
2
2
2
217
CT1
0 min
…..
30 min
Thermostat run time with faulty T1 probe.
6
6
6
6
218
CT2
0 min
…..
30 min
Thermostat off time with faulty T1 probe.
4
4
4
4
219
CSD
0 min
…..
30 min
Compressor stop delay after door has been
opened. (Only if DS = YES).
1
1
1
1
220
DFM
NON
FRO
TIM
Defrost start mode.
TIM
TIM
TIM
TIM
221
DFT
0
hours
…..
99
hours
Time interval between defrosts.
6
6
6
6
268.4
DFB
NO
…..
YES
Defrost timer clock.
YES
YES
YES
YES
206
DLI
-50
o
…..
120
o
Defrost end temperature (Only if T2 = EPO).
20
20
20
20
223
DTO
1 min
…..
120 min
Maximum defrost duration.
20
20
20
20
224
DTY
OFF
ELE
GAS
Defrost type.
OFF
OFF
OFF
OFF
225
DPD
0 sec
…..
240 sec
Evaporator pump down. Timed pause at start
of defrost.
0
0
0
0
226
DRN
0 min
…..
30 min
Drain down period.
2
2
2
2
227
DDM
RT
SP, DEF
LT
Defrost display mode.
DEF
DEF
DEF
DEF
228
DDY
0 min
…..
60 min
Defrost display delay period.
10
10
10
10
267.5
FID
NO
…..
YES
Fans in defrost.
YES
YES
YES
YES
207
FDD
-50
o
…..
120
o
Evaporator fan restart temperature following
defrost. (Only if T2 = EPO).
5
5
5
5
229
FTO
0 min
…..
120 min
Maximum evaporator fan stop period
following defrost.
3
3
3
3