Table 1 Programming of Values
Programme
Mode No.
Description Pre-programmed
standard Value
Programme Range
-10- Automatic
identification of
voltage and
current source
ON ON= automatic
OFF= manual
When “ON“, mode -11- can only
be read but not changed.
-11- Enter or read
mode of
connection
Automatic
identification
See Table 2
-12- Switching-off
time
60 From 5 to 900 seconds. *)
-13- Setting cyclic /
non-cyclic
switching
rotation
ON ON= cyclic switching
OFF= non-cyclic switching
-14- Threshold for
number of
switching
alarm
OFF From OFF to 1000 the value must
be entered in x1000 switches
-15- Cancelling
individual
switching
counters
0 Enter a number of 1-6. When
leaving this menu point the counter
of the corresponding capacitor
stage will be set to 0. Point “ALL
will reset all counters to 0.
-16- Current trans-
former Ratio
1 From 1 to 7000 in steps of 1 or at
high speed in steps of 5.*)
-17- voltage trans-
former ratio
1 From 1 to 300 in steps of 1 or at
high speed in steps of 5.*)
*) by pressing the buttons "+" or "-" for some time, the high speed mode will be activated.