Custom Energy Savings Settings
20 – SETBACK SETPOINTS / AUTO-RESTORE
00 When room is unoccupied and the thermostat is in the setback mode or turned off, it will NOT
maintain the temperature between heat and cool setback setpoints;
When guest enters the room, the thermostat will be turned off - it will not automatically
restore the most recent guest settings;
01 When room is unoccupied and the thermostat is in the setback mode or turned off, it will maintain
the temperature between heat and cool setback setpoints;
When guest enters the room, the thermostat will be turned off - it will not automatically
restore the most recent guest settings;
02 When room is unoccupied and the thermostat is in the setback mode or turned off, it will NOT
maintain the temperature between heat and cool setback setpoints;
When guest enters the room, the thermostat will automatically restore the most recent guest
settings;
03 * When room is unoccupied and the thermostat is in the setback mode or turned off, it will maintain
the temperature between heat and cool setback setpoints;
When guest enters the room, the thermostat will automatically restore the most recent guest
settings.
Set the “ SETBACK SETPOINTS / AUTO-RESTORE” to “00”, to disable EMS.
21 – TEMPERATURE CALIBRATION
-5.0 - 5.0 (0.0 °F default setting) Calibrate the temperature display: -5.0 - 5.0
°F