114 PB
COMPONENTS TESTING
Field Settings (Indoor Unit Parameter Revision)
PAR AME TE R
C O DE
PAR AME TE R
DE SC RIPTIO N
NO TE
PAR AME TE R VALUE&R E PR E SE NTATIO N
DATA
TY PE
RE PR E SE NTATIO N
(FUNC TIO N C O DE )
1
Integer
Self Recovery of
Power Break
2 Integer Temperature Type
0ļ¼Cancel Self Recovery of Power
Break function ļ¼
1ļ¼Self Recovery of Power Break ļ¼
othersļ¼invalid
3
Integer
Temperature Display
Type
0ļ¼Centigrade Temperature ļ¼
1ļ¼Fahrenheit Temperature ļ¼
othersļ¼invalid
4
0ļ¼Default display set temperature ļ¼
1ļ¼Default display room temperature ļ¼
othersļ¼invalid
Integer
Ratio of ambient
temperature sensed
by indoor
temperature
sensor(cooling
mode)
0~10valid ļ¼more than 10 default is10
0ļ¼0% ļ¼1ļ¼10% ļ¼ā¦ ļ¼10ļ¼100%
5
Filter Clean
Indication
Integer
0-entirely use
temperature
sensed b y wired
remote controller;
10- entirely use
temperature
sensed b y indoor
unit
6 Integer Filter Clean Time Set
0ļ¼Cancel Filter Clean prompt function ļ¼
1ļ¼Set Filter Clean prompt function ļ¼
othersļ¼invalid
7
0~32 ļ¼more than 32 default is 32*1000h
Integer
Installation Height
Compensation
8
Integer
0~10m ļ¼more than 10m default is 10.
=0,1,2 :no fan speed compensation;
=3: increase fan speed;
=4~10: increase more fan speed.
Cooling Temperature
Compensation
ļ¼indoor unit
temperature sensor ļ¼
9
Integer
0ļ¼0°C ; 1ļ¼ -0.5 °Cļ¼2ļ¼ -1°C
3ļ¼-1.5 ĀŗC; 4ļ¼ -2ĀŗC; 5: -2.5ĀŗC;
Heating Temperature
Compensation
ļ¼indoor unit
temperature sensor ļ¼
10 Integer Static Pressure Set
0ļ¼0°Cļ¼1ļ¼-0.5 °Cļ¼2ļ¼-1°C
3ļ¼-1.5 °C 4ļ¼ -2°Cļ¼5ļ¼-2.5 °C;
6ļ¼-3°Cļ¼7ļ¼-3.5 °C; 8: -4°C; 9: -4.5°C
10ļ¼-5°C ( the wired controller displays
intege r with the symbol )
Duct type (DC
motor )
12 Integer
1~240 ļ¼function code=static pressure
more than the limit static pressure
default the limit static pressure ļ¼Default
is 0( default static pressure, related to
models )
Ratio of temperature
sensed by indoor
temperature
sensor( (Heating
mode)
0~10valid ļ¼more than 10 default is10
0ļ¼0% ļ¼1ļ¼10% ļ¼ā¦ ļ¼10ļ¼100%
13
Charac
0-entirely use
temperature
sensed b y wired
remote controller;
10-entirely use
temperature
sensed b y indoor
unit
ter
Temperature
Adjustment-Cooling
-10~10 ī ļ¼Sing le Ch aracter with
symbol ļ¼
14
Temperature
displayed on wired
controller
Charac
ter
Temperature
Adjustment-Heating
-10~10 ī ļ¼Sing le Ch aracter with
symbol ļ¼
25
Temperature
displayed on wired
controller
Integer
Access control, ļ¬re
protection, ON/OFF
function set
=0 ļ¼Access control, ļ¬re
protection functions are all invalid ļ¼
=1 ļ¼Access control function is valid ļ¼
=2 ļ¼ļ¬re protection function is valid ļ¼
=3 ļ¼Access control, ļ¬re protection are
all validļ¼
=4 ļ¼ON/OFF function are all valid.
6 : -3ºC; 7: -3.5ºC; 8: -4°C; 9: -4.5°C
10: -5°C (The wired controller displays
integer with the symbol.)