EasyManuals Logo

Friedrich FPWC1 Service Manual

Friedrich FPWC1
148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #47 background imageLoading...
Page #47 background image
47 PB
OPERATION
Outdoor Unit Control Mode
7. Outdoor four-way Valve Control
Four-way valve of the outdoor machine shuts down when cooling but starts when heating. The operation of heating defrosting
refers to defrosting operation and, when the heating remote shutdown, the four-way valve disconnects in 50s when the
compressor stops working.
8. Start-up Protection
To prevent compressor from restart frequently in the condition that system pressure has not been completely balanced, it
can’t be restarted within 3 minutes.
9. Pressure Protection
Pressure switch is normally kept open. When the pressure grows too high, the pressure switch will close and will enter
pressure protection control. The frequency will automatically decrease. If the pressure is still unable to return to normal
condition after decreasing frequency, compressor will stop and report the fault code of pressure protection.

Table of Contents

Other manuals for Friedrich FPWC1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Friedrich FPWC1 and is the answer not in the manual?

Friedrich FPWC1 Specifications

General IconGeneral
BrandFriedrich
ModelFPWC1
CategoryAir Conditioner
LanguageEnglish

Related product manuals