Position of the primary meter at the feed-in point. *Terminating resistor R 120 Ohm
The following must be observed in a multi-meter system:
- Each Modbus address must only be assigned once.
- Terminating resistors must be positioned individually for each channel.
- The primary meter and the battery must be on different channels.
- The remaining Modbus nodes must be distributed equally.
Setting the
address of the
Fronius Smart
Meter
Symbol Name Event Function
Prog 1 x Increases the set value
Page 1 x Moves the cursor
Enter 1 x confirms the entry
1
Press "Prog" and "Page" at the same
time to enter the code.
2
Enter password "2633". Increase the
value with "Prog" and change to the
next digit with "Page".
3
Press "Prog" and "Page" at the same
time again to switch to the menu item
"Addr" (address).
4
Set the relevant address.
- Permissible values: 1 - 14
How to configure the address of the Fronius Smart Meter in the Fronius Dataman-
ager: