Parameter Range of val-
ues
Description Availability
"Mode"
Off The function is deactiv-
ated.
On (with Hys-
teresis)
Function is activated with
hysteresis.
On (without
Hysteresis)
Function is activated
without hysteresis.
In the fol-
lowing
setups "On
(without
Hysteresis)"
is not pos-
sible:
-
AUS
Region
A 2020
-
AUS
Region
B 2020
-
AUS
Region
C 2020
-
NZS
2020
"Configuration
Method"
Gradient For calculating the power
limitation depending on
the parameters "Gradient
Overfrequency" or "Gradi-
ent Underfrequency".
Stop - Fre-
quency
The gradient is calculated
automatically using the
parameters "Stop Fre-
quency - Overfrequency"
and "Power at Stop Fre-
quency - Overfrequency"
as well as "Stop Frequency
- Underfrequency" and
"Power at Stop Frequency
- Underfrequency".
"Active Grid
Support"
Off Deactivates extended act-
ive mains support for
devices with battery.
Has no in-
fluence on
the follow-
ing setups:
-
AUS
Region
A 2020
-
AUS
Region
B 2020
-
AUS
Region
C 2020
-
NZS
2020
On Activates extended active
mains support for devices
with battery.