Parameter Range of val-
ues
Description
"Recording
Probability"
If "Automatic Signal Recording (ASR)" is
activated, the frequency for a recording
can be set here.
0 No signal characteristics are recorded.
0.0 1.0 Every 10 minutes, data is uploaded to the
cloud with a frequency in accordance with
the "Recording Probability".
Example:
With a setting value of 0.1, data is up-
loaded on average every 100 minutes.
1 Data is recorded every 10 minutes.
RCMU The inverter is equipped with a universal current-sensitive residual current monit-
oring unit (RCMU) in accordance with IEC 62109-2. This unit monitors residual
currents from the PV module to the AC output of the inverter and disconnects
the inverter from the grid in the event of unauthorised residual current.
Parameter Range of val-
ues
Description
"RCMU" Off The protective function is deactivated.
Off (with
Warning)
The protective function is deactivated. The
status code 1188 is permanently displayed
on the user interface of the inverter.
On The protective function is activated.
18

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius GEN24 and is the answer not in the manual?

Fronius GEN24 Specifications

General IconGeneral
TypeHybrid Inverter
Power Range3.0 kW to 10.0 kW
Max. DC input voltage1000 V
Number of MPP Trackers2
Operating Temperature Range-25°C to +60°C
Efficiency98.2%
MPPT voltage range200 - 800 V
InterfacesWi-Fi / Ethernet / USB / RS485
Warranty5 years (extendable)
CoolingActive cooling