Parameter Range of val-
ues
Description
"Automatic Re-
connects"
If more arcs have been detected within 24
hours than are defined in "Automatic Re-
connects", the inverter will not make any
further attempt to start feeding energy in-
to the grid. The status code 1006 is dis-
played on the user interface of the invert-
er after each detection and must be ac-
knowledged manually.
Unlimited The 24 hour counter is deactivated. The in-
verter restarts feeding energy into the grid
5 minutes after each arc detected.
0 - No Recon-
nection
After an arc has been detected, no further
attempt is made to start feeding energy
into the grid and status code 1173 is dis-
played on the user interface of the invert-
er.
1 4 After a shutdown by an arc, 1, 2, 3 or 4 at-
tempts are made within 24 hours to re-
start feeding energy into the grid. After
this number of attempts, no further at-
tempt is made to start feeding energy into
the grid and status code 1173 is displayed
on the user interface of the inverter.
"Arc Logging" Enables or disables the recording of arc
signatures. The data is uploaded to the
cloud and used to continuously improve
the interference immunity and fault toler-
ance of arc detection.
Off Arc signatures are not recorded.
On Arc signatures are recorded, uploaded to
the cloud, and used to continuously im-
prove the interference immunity and fault
tolerance of arc detection.
"Automatic Sig-
nal Recording"
Activates or deactivates recording of the
inverter's signal characteristics to continu-
ously improve arc detection.
Off Recording is deactivated.
On Recording is activated. With a probability
in accordance with the "Recording Probab-
ility" parameter, data is recorded and up-
loaded to the cloud every 10 minutes.
17
EN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fronius GEN24 and is the answer not in the manual?

Fronius GEN24 Specifications

General IconGeneral
TypeHybrid Inverter
Power Range3.0 kW to 10.0 kW
Max. DC input voltage1000 V
Number of MPP Trackers2
Operating Temperature Range-25°C to +60°C
Efficiency98.2%
MPPT voltage range200 - 800 V
InterfacesWi-Fi / Ethernet / USB / RS485
Warranty5 years (extendable)
CoolingActive cooling