Example 6 Description of the parameters
P
m
Actual power at the moment the limit
value is exceeded
P
red
Reduced power
(1) "Gradient Overfrequency"
(2) "Deactivation Time"
(3) "Return Gradient 1"
(4) "Return Gradient 1 Alternative"
(5) "Return Gradient 1 Alternative
Threshold": P
m
- P
red
<= 25 %
(6) "Return Gradient 1 Alternative
Threshold": P
m
- P
red
> 25 %
(7) "Initial Delay"
The grid frequency returns to the permissible
range at P
red
.
After the waiting time (2) has elapsed, the
power is increased to the initial value P
m
with
one of the following gradients:
Gradient 1 - red
The difference between the current power
P
m
and the reduced power P
red
is ≤ "Return
Gradient 1 Alternative Threshold" of 25 % (5).
Thus, the power is increased to the initial
value P
m
with "Return Gradient 1" (3).
Gradient 2 - grey
The difference between the current power
P
m
and the reduced power P
red
is > "Return
Gradient 1 Alternative Threshold" of 25 % (5).
This increases the power to the output value
P
m
with "Return Gradient 1 Alternative" (4).
Application example with "Return Gradient 1 Alternative" and "Return Gradient 1 Alternative
Threshold".
55
EN