Potential operating range
Reactive power mode is restricted by the maximum apparent power S
n
(and the
maximum output current) as well as by the operational reactive power limits of
the inverter:
-
Primo GEN24: Q
max
= 60 % of S
n
(or cos φ = 0.80 at S
n
)
-
Symo GEN24: Q
max
= 71 % of S
n
(or cos φ = 0.70 at S
n
)
-
Tauro: Q
max
= 100 % of S
n
(or cos φ = 0.00)
The value range specified for the following parameters may be additionally lim-
ited by the selected country-specific settings.
The following figure shows the possible operating range of the inverter. All valid
operating points defined by effective power P and reactive power Q are within
the grey area.
Example: Primo GEN24
59