97
EN
452 Communication fault be-
tween filter and power 
stage set
1. Communication problem 
caused by temporary environ-
mental interference (grid, 
EMC, etc.)
1. Automatic correction
2. Check ribbon cable between 
filter PC board and power 
stage set
2. Replace ribbon cable
3. Faulty filter PC board 3. Replace filter PC board
4. Faulty power stage set 4. Replace AC PC board
453 Redundant grid monitoring 
has detected an incorrect 
grid voltage
1. Measurement fault 1. Software update
2. Grid problem 2. Automatic correction
3. Faulty AC guard on filter PC 
board
3. Replace filter PC board
4. Faulty AC guard on power 
stage set
4. Replace AC PC board
454 Redundant grid monitoring 
has detected an incorrect 
grid frequency
1. Measurement fault 1. Software update
2. Grid problem 2. Automatic correction
3. Faulty AC guard on filter PC 
board
3. Replace filter PC board
4. Faulty AC guard on power 
stage set
4. Replace AC PC board
456 Fault detected in the island-
ing monitoring
1. Occurs once 1. Restart the inverter
2. Software problem 2. Software update
3. Measurement fault on filter 
PC board
2. Replace filter PC board
4. Faulty measuring circuit for 
anti-islanding
3. Replace AC PC board
457 Grid relay does not trigger 1. Occurs once 1. Restart the inverter
2. Grid test time too short 2. Change settings
3. Grid relay jammed 3. Replace AC PC board
458 RCMU self-test failed 1. RCMU measurement fault 1. Replace filter PC board
459 Insulation measurement 
fault
1. Occurs once 1. Restart the inverter
2. Insulation measurement 
fault
2. Replace DC PC board; re-
place AC PC board if neces-
sary
460 Reference voltage outside 
the permissible limit
1. Occurs once 1. Restart the inverter
2. Faulty power stage set 
measuring circuit
2. Replace AC PC board
461 Faulty data memory 1. Faulty power stage set 1. Replace DC PC board; re-
place AC PC board if neces-
sary
462 Fault detected in monitoring 
system for DC braking
1. Occurs once 1. Restart the inverter
2. Faulty monitoring system for 
DC braking
2. Replace inverter
463 AC pin reserved 1. AC connection between 
power stage set and filter PC 
board is fitted in the wrong di-
rection (L1 and L2 swapped)
1. Check wiring
Code Description Behaviour Remedy