DC input data battery
Max. voltage 455 V
Min. voltage 150 V
Max. current 22 A
Max. output 3 000 W
DC inputs 1
AC input/output data
Nominal output power (P
nom
) 3 000 W
Max. output power 3 000 W
Rated apparent power 3 000 W
Nominal mains voltage 1 ~ NPE 220V / 230V / 240 V
Min. grid voltage
155 V
1)
Max. grid voltage
270 V
1)
Max. output current 19.4 A
Current (inrush)
6)
20 A / 1.3 ms
Nominal frequency
50 / 60 Hz
1)
Nominal frequency for Full Backup
53 / 63 Hz
1)
Initial short circuit current / phase I
K
19.4 A
Total harmonic distortion < 2 %
Power factor cos phi
2)
0.8 - 1 (adjustable)
Max. permitted mains impedance Z
max
at PCC
4)
None
Maximum output fault current / dura-
tion
29 A / 3 ms
AC output data PV Point
Max. output power 4 133 W (for 5 s)
Rated power 3 000 W
Nominal output current 13 A
Nominal mains voltage 1 ~ NPE 220 V / 230 V / 240 V
Nominal frequency
53 / 63 Hz
1)
Switchover time < 90 s
Power factor cos phi
2)
0 - 1
AC output data Full Backup
Max. output power 4 133 W (for 5 s)
Rated power 3 000 W
Nominal output current 13 A