EasyManua.ls Logo

Fronius Primo GEN24 3.6 - Protection Devices and Data Communication Interfaces

Fronius Primo GEN24 3.6
208 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AC output data Full Backup
Nominal mains voltage
1 ~ NPE 220 V
1 ~ NPE 230 V
1 ~ NPE 240 V
Nominal frequency for Full Backup
53 / 63 Hz
1)
Switchover time < 90 s
Power factor cos phi
2)
0 - 1
General data
Maximum efficiency 97.6%
European efficiency (U
mpp nom
) 96.8%
European efficiency (U
mpp max
) 95.9%
European efficiency (U
mpp min
) 95.3%
Self-consumption at night 8.2 W
Cooling Controlled forced-air ventilation
Protection class IP 66
Dimensions H x W x D 530 × 474 × 165 mm
Weight 17 kg
Inverter topology Non-insulated transformerless
Permitted ambient temperature -40 °C – +60 °C
Permissible humidity 0 - 100% (incl. condensation)
EMC emission class B
DC/AC overvoltage category
(in accordance with IEC 62109-1)
2 / 3
Pollution degree 2
Sound pressure 42 dB(A) (ref. 20µPa)
Safety class (according to IEC62103) 1
Protection devices
DC isolation measurement Warning / shutdown at R
ISO
<
100 kOHM
Overload performance Operating point shift, power limiter
DC disconnector Integrated
RCMU Integrated
RCMU classification The software class of the safety plat-
form(s) is specified as a class B con-
trol function (single channel with peri-
odic self-test) according to IEC60730
Annex H.
Active anti-islanding method Frequency conversion method
168

Table of Contents

Related product manuals