EasyManua.ls Logo

Fronius Symo Advanced 10.0-3 208-240 - Page 62

Fronius Symo Advanced 10.0-3 208-240
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
62
Fronius Symo Advanced 15.0-3 480
Input Data
MPP voltage range 350 - 800 V DC
Input voltage range (at 1,000 W/m²/14 °F in an open circuit) 200 - 1,000 V DC
Max. input current (MPP1/MPP2)
(MPP1 + MPP2)
33.0/25.0 A
51 A
Max. short circuit current of solar modules (I
SC PV
) (MPP1/MPP2) 49.5/37.5 A
Max. backfeed current from AC grid
1)
0.0 A
2)
Output Data
Nominal output power (P
nom
) 14,995 W
Max. output power (+104°F) 14,995 W
Max. output power (+140°F)
at 440 V 12,200 W
at 480 V 14,400 W
Phases 3 ~ NPE
Nominal grid voltage
at 440 V 254 V/440 V
at 480 V 277 V/480 V
Operating range AC voltage -12 ... +10%
Adjustment range for grid voltage 127 - 322 V/220 - 558 V
Max. continuous output current at V
nom
at 440 V 19.7 A
at 480 V 18.0 A
AC recommended min. overcurrent protection
at 440 V 25.0 A
at 480 V 25.0 A
Max. output residual current per duration 30.9 A/150.4 ms
Nominal frequency 50/60 Hz
Total harmonic distortion < 1.5%
Power factor (cos phi) 0 - 1 ind./cap.
3)
General Data
Maximum efficiency 98.00%
CEC efficiency
at 440 V
at 480 V 97.00%
Cooling Controlled forced-air ventilation
Protection class NEMA 4X
Dimensions h x w x d
28.5 x 20.1 x 8.9 in.
725 x 510 x 225 mm
Weight (full/lite version) 95.7/95.0 lbs. (43.4/43.1 kg)
Permissible ambient temperature -40°F to +140°F (-40°C to +60°C)
Permissible storage temperature -40°F to +158 °F (-40°C to +70 °C)
Permissible humidity 0 - 100%
Noise emission 65 dB(A) (ref. 1pW)
Protection Devices
Reverse polarity protection Integrated
Stand-alone operation protection Integrated
Arc detection/interruption Integrated

Table of Contents