The device must be installed in a clean, dry, and well ventilated standard equipment room with controllable
temperature .
Dustproof measures must be taken in the site . Dust will cause electrostatic discharges on the chassis and
affect connections of metal connectors and joints . This shortens service life of the device and may cause
failures of the device .
The equipment room must be free from leaking or dripping water, heavy dew, and damp . The temperature
and humidity in the installation site must be within specifications . For the operating temperature and
relative humidity ranges required by the device, see the device specifications . If the relative humidity
exceeds 70%, using dehumidifiers or dehumidifying air conditioners is recommended .
Corrosive gases
avoidance
The installation site must be free from acidic, alkaline, or corrosive gases.
Hardware Installation and Parts Replacement
Switch Hardware Installation and Maintenance Guide
1.2 Installation Preparation
The S5860 series switches are relatively complex devices. Before installation, careful planning and
arrangements should be made for the installation location, networking mode, power supply and wiring of the
devices. Confirm the following before installation:
1.2.1 Checking the Installation Site
Innovation · Expertise · Agility 4
1.1 Installation Procedure
Installing Modules
Installation Preparation
Installing a Switch
Post- Installation Checks
System Commissioning
Connecting a Switch
End
• The installation site provides sufficient space for heat dissipation.
• The installation site meets the temperature and humidity requirements of the switch.
• The power supply and required current are available on the installation site.
• The Ethernet cables have been deployed on the installation site.
The S5860 series switches must be installed indoors.The installation site must meet the following
requirements.
Table 1: Requirements for the Installation Site