Conformity to UL standards and Canadian standards (cUL certification) 
If installed according to the guidelines given below, inverters marked with UL/cUL are considered as 
compliant with the UL and CSA (cUL certified) standards 
Integral solid state short circuit protection does not provide branch circuit protection. Branch 
circuit protection must be provided in accordance with the National Electrical Code and any 
additional local codes. 
1. Solid state motor overload protection (motor protection by electronic thermal overload relay) 
is provided in each model. 
Adjust function codes F10 to F12 and H89 to set the protection level. 
2. Connect the power supply satisfying the characteristics shown in the table below as an input 
power supply of the inverter. (Short circuit rating) 
3. Use 75
 Cu wire only. 
4. Use Class 1 wire only for control circuits.
Short circuit rating 
When protected by class J fuses, suitable for use on a circuit capable of delivering not more 
than B rms symmetrical amperes, A volts maximum. 
Power 
supply 
voltage 
Inverter type
Power supply max. voltage 
 A (Volts) 
Power supply current 
B (Amperes)
FRN0001C2S-2U 
FRN0002C2S-2U 
FRN0004C2S-2U 
FRN0006C2S-2U 
FRN0010C2S-2U 
FRN0012C2S-2U 
Three-phase  
200V 
FRN0020C2S-2U 
240VAC 100,000 A or less
FRN0002C2S-4U 
FRN0004C2S-4U 
FRN0005C2S-4U 
FRN0007C2S-4U 
Three-phase  
400V 
FRN0011C2S-4U 
480VAC  100,000 A or less
FRN0001C2S-7U 
FRN0002C2S-7U 
FRN0004C2S-7U 
FRN0006C2S-7U 
FRN0010C2S-7U 
Single-phase  
200V 
FRN0012C2S-7U 
240VAC  100,000 A or less