186 INF-TN2FSC-E
 


Table 16-3 Contents of ow velocity distribution le
Line Row Contents
Line 2
A Describes "<Measurement result>".
B and subsequent Describes "Channel number".
C and subsequent
Channel number
126 to 1, 1 to 126 in case of connection of sensor U
1 to 126, 126 to 1 in case of connection of sensor D
1 to 126, 126 to 1 to IT row in case of connection of sensor U/D
IU Describes "<F.RATE/VEL.VALUE>".
IV Describes "<RAS>".
Line 3
B Describes "<Start/End Channel>".
C and subsequent
Describes 1 in start/end channels of channel number in line 2, and
describes 0 in others.
Line 4
A Describes "<Measurement time>".
C Describes acquisition date/hour in the "2007/10/29 10:19:44" format.
Line 5 and
subsequent
A Describes "<Velocity Prole The measurement data>".
C to IU Fluid velocity that corresponds to channel number in line 2.
IU Flow rate/uid velocity at acquisition date/hour.
IV
RAS is indicated by 32-bit binary numbers, with " " added at rst.
See "16.5.4 Regarding RAS ".


 

Bit31 0 3 71 115192327 "0" expresses normal.
"1" expresses abnormal.
□□□□□□□□□□□□□□□□□□□□□□□□□□□□□□□□
E1: Device error 1
(error in backup memory)
E1: Device error 2
(error in measurement circuit)
E2: Window scanning
E2: No received signal
E2: Received signal error
E2: Calculation error 1
(error in fluid acoustic velocity)
E2: Calculation error 2
(receiving signal overflow)
E3: Measuring range error
E3: Frequency calculation error
E3: Success rate
E4: Range over
E6: Printer fail
