5-8
Function code
Name Setting range
Min.
unit
Factory
setting
RS485
Data
format
User setting
H30
Serial link
(Function select)
Monitor, Frequency , Operation
setting command
0:
X
X
1:
X
2:
X
3:
1 0
0
H31
RS485
(Address)
1 to 31 1 1
X
0
H32
response error)
0: Immediate Er8
1: Er8 after interval set by timer
2: Retry in interval set by timer (Er8
after failure to restore)
3: Continuation of operation
1 0
0
H33
(Timer)
0.0 to 60.0s 0.1s 2.0
2
H34
(Baud rate)
0:19200[bit/s]
1:9600
2:4800
3:2400
4:1200
1 1
0
H35
(Data length)
0:8bit
1:7bit
1 0
0
H36
(Parity check)
0: None
1: Even parity
2: Odd parity
1 0
0
H37
(Stop bits)
0: 2 bits
1: 1 bit
1 0
0
H38
(No response error
detection time)
0: Not detected
1 to 60s
1s 0
0
H39
(Response interval)
0.00 to 1.00s 0.01s 0.01
4
H40
Maximum
temperature of heat
sink
Monitor only degree C
- -
0
H41
Maximum effective
current
Monitor only A - -
6
H42
Main circuit capacitor
life
Monitor only 0.1% - -
0
H43
Cooling fan operation
time
Monitor only 10h - -
0
H44
Inverter ROM version
Monitor only - - -
0
H45
Keypad panel ROM
version
Monitor only - - -
0
H46
Option ROM version
Monitor only - - -
0
Description of change during operation
: The data changed by the or key takes effect on the inverter operation. However, press the
key to store the new data.
: Press the or key to change the data. The new data takes effect after the key is pressed to
store the data.
X
: The data can be changed only while the inverter is stopped.