5-27
C05
Multistep frequency 1 through C19 Multistep frequency 15
Terminal functions SS1, SS2, SS4 and SS8 are turned on or off to switch multistep frequencies 1
through 15. (Refer to E01 through E05 for the definition of the terminal function.)
Undefined terminals among terminal functions SS1, SS2, SS4 and SS8 are assumed to be turned off.
Setting range: 0.00 to 400.0 Hz
Minimum unit: 0.01 Hz
ON ON ON ON ON ON ON ON
ON
ON ON ON ON
ON ON
ON
Output frequency (Hz)
FWD-CM
SS1-CM
SS2-CM
SS4-CM
SS8-CM
Time