2-3
Section 2 Specications
Item Specication
Type NA0AY02-MR
No. of output channels 2 channels
External load resistance Voltage output: 500
W
to 1 M
W
, Current output: 0 to 500
W
or less
Analog output range
-10 to +10V, -5 to +5V, 0 to 10V, 0 to 5V
-20 to 20mA, -10 to 10mA, 0 to 20mA, 0 to 10mA
(Collectively set for all channels by the jumper pin in the unit)
Resolution 14 bits
Overall accuracy ±1%
Data type of digital output value INT type
Output period Synchronized with the scan of the main unit.
External wire connections 8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
Applicable wire size AWG#22-18 * Be sure to use shielded twisted pair cables.
Status indication 5V power supply display, ON when normal (red)
Isolation method Not isolated * For the internal circuit, see “Appendix 2.”
Occupied words 2 words
External power supply 24V DC, 90mA *Wiring length: 10m or less
Internal current consumption 5V DC, 33mA
Dimensions 40 (W) x 90 (H) x 80 (D) (mm)
Mass Approx. 140g
(2) Analog output unit NA0AY02-MR
*1 Notes on using analog output
The analog unit does not support the hold function. If the main unit stops due to a system error, the analog output value
becomes 0 (zero). It is not possible to hold the output status after occurrence of an error or CPU stop.