(7) Resistance thermometer element input unit NA0AX06-PT
Item Specication
Type NA0AX06-PT
No. of analog input channels 6 channels
Resolution 0.1°C or 1°C *1
Applicable resistance thermometer
element
Pt100, Pt1000 (JIS or DIN)
Temperature measurement range
Pt100: -200.0 to 850.0°C (-328.0 to 1562.0°F)
Pt1000: -200.0 to 600.0°C (-328.0 to 1112.0°F)
Overall accuracy ±1% *2
Resistance of input wiring 20Ω or less
Data type of A/D conversion value INT type
Sampling period
1 second (high speed) or 2 seconds (low speed)
(Collectively set for all channels by the program loader.)
Moving average
No moving average / 2 / 4 / 8 times
(Collectively set for all channels by the program loader.)
External wire connections 8-pole terminal block (M3) x 2, Tightening torque: 0.59 to 0.78 N·m
Applicable wire size AWG#22-18 * Be sure to use shielded twisted pair cables.
Status indication 5V power supply display, ON when normal (red)
Isolation method Not isolated * For the internal circuit, see “Appendix 2.”
Occupied words 6 words
External power supply 24V DC, 16mA *Wiring length: 10m or less
Internal current consumption 5V DC, 32mA
Dimensions 40 (W) x 90 (H) x 80 (D) (mm)
Mass Approx. 140g (excl. expansion cable)
*1 The resolution is determined by the setting of the “sampling period” in the parameter.
When the resolution is 1°C: Set to “high speed.”
When the resolution is 0.1°C: Set to “low speed.”
*2 The overall accuracy is the specication for when noise described in “Electrical service conditions” is not applied.
If noise is applied, the overall accuracy may exceed the above specication.
*3 Immediately after the main unit is powered on, the A/D conversion value becomes “-32767” until the analog unit collects
analog values from external devices and starts A/D conversion (approx. 10 seconds.)
*4 If connection between the analog unit and a temperature sensor is broken, the temperature conversion value becomes
“28767.”