– 11 –
3
Chapter
Wiring
RS-485
Please use a shielded twist pair cable. (Recommended cable: KPEV-SB (made by The Furukawa Electric Co., Ltd.))
The maximum cable length should be 500m. One master and up to thirty-one micro controllers (slaves) can be connected per
circuit.
Te r minate both ends of the circuit with a terminating resistance of 100
(1/2W or more).
Ground the shielded cable once towards the master side.
SG does not have to be connected, but it can be used as an effective countermeasure against communication errors due to
noise.
Master
SG
Slave
+
+
Shielded twist pair cable
Te r minating resistance
100W (1/2W)
Te r minating resistance
100W (1/2W)
PXG Series
PXG Series
PXG Series
RS-485 interface
or
RS-485 side of
RS-232C to RS-485 converter
+
+