EasyManua.ls Logo

Fuji Electric PXG-9 - Word Data (Read;Write): Function Code 03 (H), 06 (H), 10 (H)]

Fuji Electric PXG-9
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
– 43 –
7
Chapter
Word Data (read/write): function code [03 (H), 06 (H), 10 (H)]
Operation (Ch1)
Parameter
display
Parameter
name
Contents
Relative
address
Resistor Number
Type Read data
Written data
range
Factory
Setting
Dependent
on range
Internal
Engineering
unit
"
MM
MM
aa
aa
nn
nn
"
MAn Switches to manual mode 0088
H
40121 41121 Word 0: oFF (during auto)
1: on (during manual)
0: oFF (auto)
1: on (manual)
oFF
"
SS
SS
TT
TT
bb
bb
YY
YY
"
STbY Switches between RUN
and standby
0003
H
40004 41004 Word 0: oFF (during RUN)
1: on (during standby)
oFF
"
rr
rr
EE
EE
MM
MM
"
rEM Switches to remote mode 0084
H
40117 41117 Word
0: LoCL (during Local)
1: rEM (during Remote)
0: LoCL (Local)
1: rEM (Remote)
LoCL
"
PP
PP
rr
rr
GG
GG
"
PrG Ramp/soak controls
Command
0061
H
40082 41082 Word 0: oFF (during stop)
1: rUn (during run)
2: hLd (during hold)
0: oFF (stop)
1: rUn (run)
2: hLd (hold)
oFF
"
AA
AA
tt
tt
"
AT Auto-tuning
run command
0004
H
40005 41005 Word 0: oFF
1: rUn
2: Low
oFF
"
LL
LL
AA
AA
CC
CC
hh
hh
"
LACh Cancels the DO output
latch Command
00B0
H
40161 41161 Word 0: oFF
1: rST (latch reset)
oFF
"
SS
SS
vv
vv
nn
nn
"
Svn
Selectable SV numbers
00F2
H
40221 41221 Word 0: Sv0 (Local SV)
1: Sv1 (SV = SV-1)
2: Sv2 (SV = SV-2)
3: Sv3 (SV = SV-3)
4: Sv4 (SV = SV-4)
5: Sv5 (SV = SV-5)
6: Sv6 (SV = SV-6)
7: Sv7 (SV = SV-7)
8: di : SV = choose Di
Sv0
"
PP
PP
LL
LL
nn
nn
11
11
"
PLn1
Currently selected PID No.
00F3
H
40222 41222 Word 0: PID0 (PID group local)
1: PID1 (PID group No. 1)
2: PID2 (PID group No. 2)
3: PID3 (PID group No. 3)
4: PID4 (PID group No. 4)
5: PID5 (PID group No. 5)
6: PID6 (PID group No. 6)
7: PID7 (PID group No. 7)
8: di (PID group Di selection)
PID0
"
AA
AA
LL
LL
11
11
"
AL1 ALM1 set value or A1-L 003B
H
40044 41044 Word 0% to 100% FS 10°C
"
AA
AA
LL
LL
11
11
LL
LL
"
AL1L AL1L set value 00B2
H
40163 41163 Word 0% to 100% FS (absolute alarm)
-100% to 100 % FS (deviation alarm)
"
AA
AA
LL
LL
11
11
hh
hh
"
AL1h AL1h set value 00B3
H
40164 41164 Word 0% to 100% FS (absolute alarm)
-100% to 100 % FS (deviation alarm)
"
AA
AA
LL
LL
22
22
"
AL2 ALM2 set value or A2-L 003C
H
40045 41045 Word 0% to 100% FS 10°C
"
AA
AA
LL
LL
22
22
LL
LL
"
AL2L AL2L set value 00B9
H
40170 41170 Word 0% to 100% FS (absolute alarm)
-100% to 100 % FS (deviation alarm)
"
AA
AA
LL
LL
22
22
hh
hh
"
AL2h AL2h set value 00BA
H
40171 41171 Word 0% to 100% FS (absolute alarm)
-100% to 100 % FS (deviation alarm)
"
AA
AA
LL
LL
33
33
"
AL3 ALM3 set value or A3-L 003D
H
40046 41046 Word 0% to 100% FS 10°C
"
AA
AA
LL
LL
33
33
LL
LL
"
AL3L AL3L set value 00C0
H
40177 41177 Word 0% to 100% FS (absolute alarm)
-100% to 100 % FS (deviation alarm)
"
AA
AA
LL
LL
33
33
hh
hh
"
AL3h AL3h set value 00C1
H
40178 41178 Word 0% to 100% FS (absolute alarm)
-100% to 100 % FS (deviation alarm)
"
AA
AA
LL
LL
44
44
"
AL4 ALM4 set value or A4-L 00C7
H
40184 41184 Word 0% to 100% FS 10°C
"
AA
AA
LL
LL
44
44
LL
LL
"
AL4L AL4L set value 00C7
H
40184 41184 Word 0% to 100% FS (absolute alarm)
-100% to 100 % FS (deviation alarm)

Related product manuals