EasyManua.ls Logo

Fuji Electric PXG-9 - Engineering Unit Data Address Map

Fuji Electric PXG-9
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
– 66 –
7
Chapter
Engineering Unit Data Address Map
Handles data dependent on an input range as a scaled value (engineering unit).
See "Operation Manual" for more details about individual parameter functions and settings ranges.
Bit Data (read only): function code [02 (H)]
Relative
address
Coil
Number
Type
Memory
contents
Read data
Dependent
on range
Remarks/
related
parameters
0000
H
10001 bit ALM1 ON/OFF 0: Alarm OFF
1: Alarm ON
00001
H
10002 bit ALM2 ON/OFF 0: Alarm OFF
1: Alarm ON
00002
H
10003 bit ALM3 ON/OFF 0: Alarm OFF
1: Alarm ON
00003
H
10004 bit ALM4 ON/OFF 0: Alarm OFF
1: Alarm ON
00004
H
10005 bit ALM5 ON/OFF 0: Alarm OFF
1: Alarm ON
00005
H
10006 Not used
00006
H
10007 Not used
00007
H
10008 Not used
00008
H
10009 bit D01 ON/OFF 0: DO OFF
1: DO ON
00009
H
10010 bit D02 ON/OFF 0: DO OFF
1: DO ON
0000A
H
10011 bit D03 ON/OFF 0: DO OFF
1: DO ON
0000B
H
10012 bit D04 ON/OFF 0: DO OFF
1: DO ON
0000C
H
10013 bit D05 ON/OFF 0: DO OFF
1: DO ON

Related product manuals