– 35 –
6
Chapter
Example of Transmitting a Message
This example explains how to set PID parameter "P" to 100.0 (1000D = 03E8H) on station number 1.
Parameter "P" relative address: 0005H (internal calculation value table)
03EDH (initial value table)
Point
For more about the internal calculation value, engineering unit, and decimal point see "Transmission Data
Format" (p. 40).
Master Slave
Command Message (bytes)
Station No. 01H
Function Code 06H
Specified Write
Number
(Relative Address)
Upper number 00H
Lower number 05H
Word Data to Write
Upper number 03H
Lower number E8H
CRC Data
Upper number 99H
Lower number 75H
Response Message (bytes)
Station No. 01H
Function Code 06H
Specified Write
Number
(Relative Address)
Upper number 00H
Lower number 05H
Write Specification
State
Upper number 03H
Lower number E8H
CRC Data
Upper number 99H
Lower number 75H