– 37 –
6
Chapter
Example of Transmitting a Message (Internal Calculation Data)
The message is composed as follows when writing the following PID parameters to station number 1.
P = 100.0 (= 1000D = 03E8H)
I = 10 (= 100D = 0064)
D = 5.0 (= 50D = 0032H)
•Parameter “PP
PP
” relative address: 0005H, Data number: 03H
Point
The decimal point cannot be included in the sent data, so data such as “100.0” above is sent as “1000”.
Refer to
For each type of send data format, see “Chapter 7, Address
Map and Data Configuration” (p. 39).
Master Slave
Command Message (bytes)
Station No. 01H
Function Code 10H
Specified Write
Number (Relative
Address)
Upper number 00H
Lower number 05H
No. of Words to
Write
Upper number 00H
Lower number 03H
No. of Bytes to Write 06H
First Word Data to
Write
Upper number 03H
Lower number E8H
Next Word Data to
Write
Upper number 00H
Lower number 64H
Last Word Data to
Write
Upper number 00H
Lower number 32H
CRC Data Upper number 56H
Lower number BEH
Response Message (bytes)
Station No. 01H
Function Code 10H
Specified Write
Number
(Relative Address)
Upper number 00H
Lower number 05H
Write Specification
State
Upper number 00H
Lower number 03H
CRC Data
Upper number 90H
Lower number 09H