EasyManua.ls Logo

Fujitsu Airstage J-II - SC.HE. Liquid Outlet Sensor Error

Fujitsu Airstage J-II
209 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SC.HE. Liquid Outlet Sensor Error
OK
DC
CN142
THERMISTOR
(SC.INT.GAS)
THERMISTOR
(SC.EXT.GAS)
THERMISTOR
(SC.EXT.LIQ)
< TH7 >
B
L
A
C
K
B
L
A
C
K
B
L
A
C
K
B
L
A
C
K
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
BLA
CK
BLA
CK
Liquid pipe temperature thermistor
SC.HE.Liquid Outlet temperature thermistor 2 short or open detected
1. Connector connection defective, open
2. Thermistor defective
3. Main PCB defective
OK
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
Check Point 2 : Check the thermistor
Thermistor characteristics check (Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 22".
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Main PCB (CN142:3-4) voltage value = 5V
Remove the thermistor from Main PCB, check the voltage.
Liquid pipe temperature sensor 2 (CN142:3-4)
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. 83. 2
Error Code : 83
04-39
Trouble shooting 29
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :

Table of Contents