Trouble shooting 4
INDOOR UNIT Error Method:
Room Temperature Sensor Error
Indicate or Display:
Indoor Unit : Operation LED 4 times Flash, Timer LED 1 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 4 1
Detective Actuators:
Indoor Unit Controller PCB Circuit
Indoor Temperature Thermistor
Detective details:
When Indoor thermistor open or shortage is detected at power ON.
Forecast of Cause :
1. Connector defective connection 2. Thermistor defective 3. Controller PCB defective
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
6.5
35
8.0
30
10.012.515.820.125.233.6Resistance Value ( )
2520151050
Temperature (°C)
3.54.35.3Resistance Value ( )
504540
Temperature (°C)
OK
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Small size Wall mount Schematic Diagram(Direct soldering to PCB)
If the voltage does not appear, replace Controller PCB and set up the original address.
H/E Inlet Thermistor
(CN20 Wire:Black)
H/E Outlet Thermistor
(CN20 Wire:Gray)
Room Temp. Thermistor
(CN19 Wire:Black)
Room Temp. Thermistor
(CN10 Wire:Black)
H/E Intlet Thermistor
(CN12 Wire:Black)
H/E Outlet Thermistor
(CN11 Wire:Gray)
DC
Cassette Schematic Diagram (Connector connection)
Wall mount Schematic Diagram (Connector connection)
H/E Outlet Thermistor
(CN9 Wire:Gray)
H/E Inlet Thermistor
(CN9 Wire:Black)
Room Temp. Thermistor
(CN8 Wire:Black)
H/E Outlet Thermistor
(CN17Wire:Gray)
H/E Inlet Thermistor
(CN17 Wire:Black)
Room Temp. Thermistor
(CN16 Wire:Black)
04-14
Duct Schematic Diagram (Connector connection)