04-107
SERVICE PARTS INFORMATION 17
ACTPM
(Active Filter Module)
Check Point 1 : Appearance check
No fissures, breaks, damage, etc. at the body and terminals section?
ACTPM
Check Point 2 : Electric check
Disconnect the connection wires.
Set the tester to the "Resistance" mode, and measure
the resistance between the following terminals.
Judge the result of as follows:
All 3 points several M or greater : Normal
1 or more points several k to short : Defective
(+IN) - (-IN)
L1 - L2
P - N
Check Point 3
L2 P
Set the tester to the "Diode" mode, and measure the voltage value between the following terminals.
Several 0.3V to 0.7V : Normal
Under 0.1V or over load : Defective
Judge the result of as follows:
Tester +side
(red)
Tester - side
(black)
Tester display
[V]